FORTRON CHAMP 6K TOWER ONLINE Product ID: 70293 Mnfr. Part#: CHAMP 6K TOWER ONLINE • Color: Black • Weight: 61 kg • Manufacturer: FORTRON • Capacity: 6000 VA / 5400 W • Input: Low Line Loss: 110 VAC ± 3 % at 50% Load;176 VAC ± 3 % at 100% Load;Low Line Comeback: Low Line Loss Voltage + 10V;High Line Loss: 300 VAC ± 3 %;High Line Comeback: High Line Loss Voltage - 10V;Frequency Range: 46Hz ~ 54 Hz @ 50Hz system, 56Hz ~ 64 Hz @ 60Hz system;Phase: Single phase with ground;Power Factor: ? 0.99 at 100% Load • Output: Output voltage: 208/220/230/240VAC;AC Voltage Regulation: ± 1%;Frequency Range (Synchronized Range): 46Hz ~ 54 Hz @ 50Hz system, 56Hz ~ 64 Hz @ 60Hz system;Frequency Range (Batt. Mode): 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz;Overload:;AC mode: 100%~110%: 30min; 110%~130%: 5min; >130% : 10sec;Battery mode: 100%~110%: 3min; 110%~130%: 30sec; >130% : 10sec;Current Crest Ratio: 3:1 max;Harmonic Distortion: ? 3 % THD (Linear Load), ? 5 % THD (Non-linear Load) • Battery: Standard Model:;Battery Type: 12 V / 9 Ah;Numbers: 16;Recharge Time: 9 hours recover to 90% capacity;Charging Current: Default : 1 A ± 10%, Max.: 1A, 2A (Adjustable);Charging Voltage: 218.4V ± 1%;Long-run Model:;Battery Type: Depending on applications;Numbers: 16-20;Charging Current: Default: 4 A ± 10%, Max.: 1A, 2A, 4A, 6A (Adjustable, 6A is only available for 16pcs batteries);Charging Voltage: 218.4V ± 1% (based on 16pcs batteries) • Environment: Operation Temperature: 0 ~ 50°C (battery life cycle will be shorten when temperature is above 25°C);Operation Humidity: < 95 % and non-condensing;Operation Altitude**: <1000m;Acoustic Noise Level: Less than 55dB @ 1 Meter • Dimensions: 369 x 190 x 688mm • Warranty: 24 Months https://www.fsp-group.com/en/product/ups/1489375278-407.html FORTRON CHAMP 6K TOWER ONLINE
|